Questions & Responses Released to All Sellers
![]() |
Buy #: 1075352
|
Question Deadline:
08/16/2021 11:00 ET
|
Question Count: 3
|
![]() |
Buy #: 1075352
|
Question Deadline:
08/16/2021 11:00 ET
|
Question Count: 3
|
Question Submitted:
SOW is asking for two circuit breakers… That means one in the generator and the other a service entrance circuit breaker which is an ATS with a breaker in the entrance, can you please confirm?
Response Received:
Confirmed. But the breaker at the ATS shall have the capability to be manually operated and separated from the ATS. Cannot be inside the ATS. This is in order to be able to access the ATS when interrupting by this breaker.
|
Question Submitted:
Please confirm if you are requesting that the unit is delivered with it own 400Amp Circuit Braker onboard, and an additional enclosed Main breaker 400 amps, 120/208volts, NEMA 3R as described on item #3 of the request.
Response Received:
That is correct. The additional enclosed main breaker was also requested.
|
Question Submitted:
The scope of this bid is only for the supply of the generator without installation. Please confirm the delivery address. Will the generator be installed inside a room or outside on a concrete pad?
Response Received:
This bid is only for supply of 100Kw Generator. To be delivered to - 225 Double Eagle Ave., Fort Buchanan Puerto Rico 00934. It will be installed outside on a concrete pad.
|
Unison Marketplace Process Help
Help and Training page which includes training videos, interactive help, and more. A link can also be found on the top right of every page, after log in.
For additional information, please contact:
Marketplace Support
Tel: (877) 933-3243
Contact Marketplace Support
For additional information, please contact:
Marketplace Support
Tel: (877) 933-3243
Contact Marketplace Support