Question Submitted:
1-Circuit breaker size is 600A - on the generator? Or on the Transfer Switch (making it Service Entrance)? 2-What Amperage is the Transfer Switch supposed to be?
Response Received:
1-ATS do not needs to be Service entrance. The building has already a 600 amps main breaker. 2-600 amps ATS.
Question Submitted:
Is a wind rated enclosure required?
Response Received:
They should comply with UL 2200.
Question Submitted:
Fuel type is diesel?
Response Received:
YES.