Question & Responses for Buy # 1070514

Questions & Responses Released to All Sellers
Buy #: 1070514
Question Deadline:  07/06/2021 11:00 ET
Question Count: 8
Buy #: 1070514
Question Deadline:  07/06/2021 11:00 ET
Question Count: 8
Question Submitted:
1-Circuit breaker size is 400A - on the generator? Or on the Transfer Switch (making it Service Entrance)? 2-What Amperage is the Transfer Switch supposed to be?
Response Received:
1-In the generator. ATS do not needs to be Service entrance. The building has already a 300 amps main breaker. 2-400 amps ATS
Question Submitted:
Once contract gets awarded, what would be delivery timeline?
Response Received:
120 days if possible. It may be negotiated.
Question Submitted:
Please specify what manufactures tests for generator?
Response Received:
Onsite factory acceptance tests that certifies and ensures that the set will function.
Question Submitted:
This generator should be rated for prime or standby operation?
Response Received:
This generator will be used as a stationary unit for backup power.
Question Submitted:
Are you seeking a Stationary unit as backup power or a mobile unit to be used as prime power?
Response Received:
Stationary unit as backup power.
Question Submitted:
Does it have to be a diesel Generator?
Response Received:
Yes.
Question Submitted:
Special delivery instructions?
Response Received:
Item shall be delivered to the building site at Fort Buchanan, Puerto Rico. No installation required.
Question Submitted:
Does it require Generator installation at site?
Response Received:
No. Generator purchase only, including delivery to the location at Fort Buchanan, Puerto Rico. No installation required.