Question Submitted:
Will a full time QC/Super/SSHO (Triple Hat) be required on site during construction?
Response Received:
Yes, one person "triple hatting" is fine for this small project
Question Submitted:
It boggles the mind that the government did not change the bidding date. We have not heard of any question being asked or posted as of today.from the walk thru The original specs went from crasiness to a complicated specs.. No supplier will give us a quote in one day minimum one week. More questions need to be answered The crawl space dimensions are not stated Are we crawling in mud or concrete floor. No dimensions for crawl space Provide controls engineering and drawings. This is not a design build projects it is a fixed contract is the controls engineering for room 117 only. What drawing are they looking for need clarification. This is a complicated request it just cannot be in a short time These are just a few there is more but no sense asking since it is bid tomorrow. Thanks for listening
Response Received:
Yes, the controls engineering is for room 117 only. This project does not extend beyond room 117. The Q&A period has ended & no further questions are permitted.
Question Submitted:
Please clarify condensate requirements form AHU 44 to which area or POC.
Response Received:
Under floor to existing condensate line. No further questions are permitted.
Question Submitted:
Please clarify the piping will be externally mounted on the existing walls and into space above 24”x24” ceiling tiles.
Response Received:
Piping will run under floor and up front wall into AHU 4. No further questions are permitted.
Question Submitted:
Will vendor provide the vibration isolation/seismic (if required) design for the new fan Coil? We assume this is ceiling mounted.
Response Received:
No. Will be mounted from ceiling beams and hung with vibration isolators. No further questions are permitted.
Question Submitted:
Plans show 24”x24” lay in ceiling tiles in area of work. Please clarify that vendor will remove required sections for new unit install requirements
Response Received:
Yes. No further questions are permitted.
Question Submitted:
It is assumed that M28 on M-101 is not valid.
Response Received:
Correct. No further questions are permitted.
Question Submitted:
Will there be a secondary drain pan required?
Response Received:
Yes. No further questions are permitted.
Question Submitted:
Will air balance be required?
Response Received:
Yes. No further questions are permitted.
Question Submitted:
QUESTION FROM SELLER: Statement of Work Section 2: Scope - Bullet #2 - Please confirm that there is no hot water connection to the new AHU-4, only chilled water connections based on the scope of work and discussions on site? Drawing M-102 shows otherwise. Response See Below
Response Received:
There is no hot water to be used in AHU-4, only chill water. Heat will be supplied from heat strips in the AHU. Electrical for the heat strip will need to be done by other in house personnel.
Buy #: 1183454_01
Question Deadline:  09/05/2024 14:00 ET
Question Count: 0
Buy #: 1183454_01
Question Deadline:  09/05/2024 14:00 ET
Question Count: 0
The Buyer has not released any questions/responses to all Sellers for this Buy.
Buy #: 1183454
Question Deadline:  08/29/2024 14:00 ET
Question Count: 0
Buy #: 1183454
Question Deadline:  08/29/2024 14:00 ET
Question Count: 0
The Buyer has not released any questions/responses to all Sellers for this Buy.
Unison Marketplace Process Help
Help and Training page which includes training videos, interactive help, and more. A link can also be found on the top right of every page, after log in.

For additional information, please contact:

Marketplace Support
Tel: (877) 933-3243
Contact Marketplace Support